WhatsApp
🌞 Limited-Time Offer: Get 35% OFF Solar Water Heater Systems! View Offer
Close menu

Pecol PHM Commercial Heat Pump Water Heater (3–20 HP)

The PHM is Pecol's own commercial heat pump for centralised hot water, designed for the tropics. It saves about 75% on heating bills compared with electric heating, and gives free cold air as a bonus.

Pecol PHM Commercial Heat Pump

Overview

Three-phase 415V heat pump for central hot water, about 75% savings on heating bills. The PHM Commercial Heat Pump is part of Pecol's Commercial Heat Pumps range (commercial hot water heat pumps). Size range: 3 – 20 HP.

Models: PHM 3, PHM 5, PHM 7.5, PHM 10, PHM 15, PHM 20

All details on this page come from the Pecol commercial heat pump brochure. Download the Commercial heat pump brochure (PDF) for drawings and installation notes.

Key features

Lowest operating cost

Moves surrounding heat into the water instead of making heat with electric resistance, gas or oil. Pay less than one third of your heating bill.

Pollution free and safer

No natural gas, LP gas or diesel, so no fire-proof room, fuel pipes or back-draft danger.

Practically maintenance free

Fully automatic operation needing minimal maintenance.

Free cold air

The large flow of cold air can be ducted to cool a laundry, lift motor room or kitchen.

Space flexibility

The heat-absorbing unit, compressor unit and calorifier can sit in different rooms, joined by refrigerant copper piping.

Built for the tropics

Components from major manufacturers in the USA and Japan, with in-house before and after service.

Technical specifications

PHM specifications
ModelCompressor (kW / HP)Power supplyDimension L × W × H (mm)Weight (kg)Output Class I, COP 5 (BTU/hr)Output Class II, COP 4 (BTU/hr)Output Class III, COP 3 (BTU/hr)
PHM 32.25 / 3Three phase, 415V, 50Hz1067 × 890 × 48316038,38530,70823,031
PHM 53.75 / 5Three phase, 415V, 50Hz1220 × 1169 × 72421063,97551,18038,385
PHM 7.55.62 / 7.5Three phase, 415V, 50Hz1220 × 1169 × 72426095,87876,70257,526
PHM 107.50 / 10Three phase, 415V, 50Hz1372 × 1169 × 800300127,950102,36076,770
PHM 1511.25 / 15Three phase, 415V, 50Hz1372 × 1169 × 800330191,925153,540115,155
PHM 2015 / 20Three phase, 415V, 50Hz1372 × 1169 × 800400255,900204,720153,540

Special capacities and dimensions can be made to requirement.

Choosing the class
ClassTemperature riseCOP
Class I18°C5.0 – 8.0
Class II33°C3.3 – 5.0
Class III43°C3.0 – 3.5

In the tropics, heating 27°C water to 60°C is a 33°C rise, so a Class II heat pump is needed. The compressor size depends on the recovery rate and storage capacity.

Specifications are from the manufacturer's brochure and may change without notice. Please confirm with our engineers before ordering.

Where it is used

  • Hotels and resorts (used at Sheraton Subang, Sama-Sama KLIA and The Ascott Kuala Lumpur)
  • Hospitals (Subang Jaya Medical Centre)
  • Hostels, factories, laundries and commercial kitchens

PHM Commercial Heat Pump price and quotation

Prices depend on the size, installation and site conditions, so we quote each project individually. Tell us how many people or rooms you need hot water for, and our engineers will recommend the right model and send you a free quotation.

WhatsApp us for a quotation, call +6012-387 9188 or use the contact form. Pecol also provides maintenance and spare parts in Malaysia.